![Atmos ACD 03 Скачать руководство пользователя страница 259](http://html.mh-extra.com/html/atmos/acd-03/acd-03_operation-manual_3003627259.webp)
Operation manual - EN
www.atmos.eu
EN - 259
ACD03/04
12. OVERVIEW OF MENUS AND THEIR PARAMETERS
SYSTEM menu
Parameter Description
Setting range / Setting value
Factory default setting
Setting
P01
Language
-
-
P02
Enabling planning of weekly programs
1 - week A
2 - week A, B, C
1 - week A
P04
Temperature of transition to summer mode
(P05 + 1 K) ‒ 40
20 °C
P05
Antifreeze protection temperature
-20 ‒ (P04 - 1 K)
-5 °C
P07
Enabling the temperature of comfort block
of time program
Off / On
On
P08
Fixed outdoor temperature
-20 ‒ 20 °C
0,0 °C
P09
Climate zone
-20 ‒ 20 °C
-12 °C
P10
Building type
1 – light
2 – medium
3 – heavy
2 – medium
P11
Automatic exit menu time
1 ‒ 60 min
5 min
P12
Anti-blocking protection
Off / On
Off
P13
Logical alarms display
Off / On
Off
P14
Information - last position
Off / On
Off
P15
Password for user (child protection function) -
0
P16
Password for technician
-
-
P17
Password for OEM
-
-
P18
Proposed room temperature
0 ‒ 30 °C
20 °C
P20
Screen brightness settings
10 ‒ 100 %
100 %
P21
Screen brightness settings - screensaver
10 ‒ 40 %
15 %
P25
Antifreeze protection - run
1 ‒ 120 min
Off (20 min)
P26
Antifreeze protection - pause
1 ‒ 120 min
Off (60 min)
P28
Default parameter values
P29
Controller factory setting (reset)
P30
Back up / System Recovery
Recovery
Back up
P31
Program update
12. Overview of menus and their parameters