Operation manual - EN
www.atmos.eu
EN - 221
ACD03/04
Sources
(Access level - User - P37 / Service technician - everything)
The setting is done with the button (to enter the menu), under which click on the symbol for
Sources.
Use the
Sources
menu to set parameters associated with secondary power sources. It is displayed after
activating the external boiler function in the
→ →
Hydraulics menu, Function configuration/
Sources/EKx - external boiler submenu, or activating the electric heating of the accumulation tank
in the
→ →
Hydraulics menu, Accumulation tank/EHP - electric heating of accumulation tank
submenu.
Parameters:
• P04
Sources
parameter - EKstart default temperature
The parameter is intended to set the switching temperature of the EKP external boiler pump and
the temperature to enable the operation of heating circuits and DHW heating circuit.
Factory default setting: 40 °C
INFO
- P04
Sources
, P05
Sources
, P06
Sources
, P07
Sources
, P08
Sources
a P16
Sources
parameters are visible
only after the activation of the EKx external boiler function.