RP/IS-A-4000SS

4000SS-OSY with Flood Sensor

NOTICE

For Australia and New Zealand, line strainers should be installed 

between the upstream shutoff valve and the inlet of the backflow 

preventer.

Fittings such as end connectors intended to join alternative pipe 
systems made from other materials (such as plastics) shall also conform 
to the relevant dimensional and performance requirements of the 
appropriate Australian, New Zealand, or joint Australian–New Zealand 
Standard for the alternative pipe system.

Testing

For field testing procedure, refer to Ames installation sheets  

IS-A-ATG-1 at www.amesfirewater.com.
For other repair kits and service parts, refer to our Backflow  

Prevention Products Repair Kits & Service Parts price list  

PL-A-RP-BPD at www.amesfirewater.com.
For technical assistance, contact your local Ames representative.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can 

result in death, serious personal injury, property damage, or 

damage to the equipment.
Keep this Manual for future reference.

You are required to consult the local building and plumbing 

codes prior to installation.  If the information in this manual 

is not consistent with local building or plumbing codes, 

the local codes should be followed. Inquire with governing 

authorities for additional local requirements.

WARNING

!

Need for Periodic Inspection/Maintenance:

  This product must 

be tested periodically in compliance with local codes, but at least 

once per year or more as service conditions warrant. If installed on 

a fire suppression system, all mechanical checks, such as alarms 

and backflow preventers, should be flow tested and inspected in 

accordance with NFPA 13 and/or NFPA 25. All products must be 

retested once maintenance has been performed. Corrosive water 

conditions, and/or unauthorized adjustments or repair could render 

the product ineffective for the service intended. Regular checking 

and cleaning of the product’s internal components helps assure 

maximum life and proper product function.

WARNING

!

WARNING

!

The installation and maintenance of backflow assemblies 

should be performed by a qualified, licensed technician.  

Failure to do so may result in a malfunctioning assembly.

Installation, Maintenance, and Repair Manual

Series 4000SS

Reduced Pressure Zone Assemblies
8" – 12"

Series 4000SS sizes 8" to 10" include a flood sensor that detects 

excessive relief valve discharges and triggers notification of potential 

flood events. 
 

NOTICE

An add-on connection kit is required to activate the flood sensor. 

Without the connection kit, the flood sensor is a passive component 

and will not communicate with any other device. (A retrofit sensor 

connection kit is also available for existing installations. See “Add-on 

and Retrofit Sensor Connection Kits,” for ordering details.)

NOTICE

Use of the flood sensor does not replace the need to comply with all 

required instructions, codes, and regulations related to installation, 

operation, and maintenance of this product, including the need to 

provide proper drainage in the event of a discharge. 

 

Watts

®

 is not responsible for the failure of alerts due to  

connectivity issues, power outages, or improper installation.

Содержание AMES 4000SS Series

Страница 1: ...er year or more as service conditions warrant If installed on a fire suppression system all mechanical checks such as alarms and backflow preventers should be flow tested and inspected in accordance w...

Страница 2: ...Local water authorities must approve all installation configurations Allow sufficient clearance around the installed assembly to conduct testing servicing and inspection Allow a minimum of 12 from the...

Страница 3: ...stream to make the clapper parallel to the valve body See Figure 3 Bring the check assembly through the check retaining wall leaving the check assembly parallel to the valve body Pull the check assemb...

Страница 4: ...op 3 8 nut and back it off without unscrewing the threaded rod from the spider Place a box end wrench or crescent wrench on the 3 8 nut closest to the spring retaining plate and tighten Tighten the th...

Страница 5: ...on the open end of the diaphragm with the cupped hand The trapped air in the dia phragm forces the diaphragm between the inside of the sleeve and the outside of the piston Ensure that the diaphragm is...

Страница 6: ...be tight against reverse flow under all pressure differentials Close high valve A and open test cock No 2 Close test cock No 4 Disconnect vent hose at test cock No 4 Open valves B and C bleeding to at...

Страница 7: ...ure Leak through diaphragm or around flange bolt holes of relief valve Service relief valve Pressure relief valve does not close See problem Pressure relief valve does not close Assembly discharges fr...

Страница 8: ...RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT RP IS A 4000SS 2348 7020351 2023 Watts USA Backflow T 978 689 606...