Parameters 417
Specifies more hardware-related options that require
differentiated parameter defaults. See parameter
WARNING!
After switching any bits in this word,
recheck the values of the affected parameters.
Note:
This parameter cannot be changed while the drive is
running.
-
0000h…FFFFh
Hardware options configuration word 2.
1 = 1
(Only visible with a BCU control unit)
Filters the list of drive/inverter types listed by parameter
.
Note:
This parameter cannot be changed while the drive is
running.
No filter
All types listed.
1
-3 (380-415V)
-3 (380…415 V) types listed.
2
-5 (380-500V)
-5 (380…500 V) types listed.
3
-7 (525-690V)
-7 (525…690 V) types listed.
4
-7 LC (525-690V)
Liquid-cooled -7 (525…690 V) types listed.
5
(Only visible with a BCU control unit)
Defines the drive/inverter type if it consists of parallel-
connected modules.
If the drive/inverter consists of a single module, leave the
value at
.
Note:
This parameter cannot be changed while the drive is
running.
Not selected
The drive/inverter does not consist of parallel-connected
modules, or type not selected.
0
[Drive/inverter type] Drive/inverter type consisting of parallel-connected modules.
-
Defines the ratio of the step-up transformer.
0.000
0.000 … 100.000
Step-up transformer ratio.
1000 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
Dual use
1 = Dual use active. For drives with N8200. (Allows higher
output speeds/frequencies and speed/frequency reference limits.)
1
SynRM
1 = Synchronous reluctance motor used. Affects parameters
2
Salient PM
1 = Salient-pole permanent magnet motor used. Affects parameters
3
LV Synchro
1 = Externally-excited synchronous motor used. Requires a license.
Contact your local ABB representative for more information.
4
Aux fan 1
supervision
1 = Auxiliary fan 1 installed and supervised.
5
Aux fan 2
supervision
1 = Auxiliary fan 2 installed and supervised.
6…15
Reserved
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...