130 Parameters
Displays the age of the auxiliary cooling fan as a percentage
of its estimated lifetime. The estimate is based on the duty,
operating conditions and other operating parameters of the
fan. When the counter reaches 100%, a warning (
) is generated.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…150%
Auxiliary cooling fan age.
1 = 1%
(Only visible when IGBT supply unit control activated by
)
Estimated supply unit temperature in percent of fault limit.
0.0% = 0 °C (32 °F)
94% approx. = Warning limit
100.0% = Fault limit
-
-40.0 … 160.0%
Supply unit temperature in percent.
1 = 1%
(Only visible when IGBT supply unit control activated by
)
Counts the closures of the main circuit breaker of the supply
unit.
-
0…4294967295
Count of closures of main circuit breaker.
1 = 1
06
Drive control and status words.
The main control word of the drive. This parameter shows the
control signals as received from the selected sources (such as
digital inputs, the fieldbus interfaces and the application
program).
The bit assignments of the word are as described on page
. The related status word and state diagram are presented
respectively.
Notes:
• Bits 12…15 can be used to carry additional control data,
and used as a signal source by any binary-source selector
parameter. Bit 10 must be active for bits 12…15 to update.
• In fieldbus control, this parameter value is not exactly the
same as the control word that the drive receives from the
PLC. See parameter
This parameter is read-only.
-
0000h…FFFFh
Main control word.
1 = 1
The drive control word received from the application program
(if any). The bit assignments are described on page
This parameter is read-only.
-
0000h…FFFFh
Application program control word.
1 = 1
FBA A transparent
control word
Displays the unaltered control word received from the PLC
through fieldbus adapter A when a transparent
communication profile is selected eg. by parameter group
. See section
This parameter is read-only.
-
00000000h …
FFFFFFFFh
Control word received through fieldbus adapter A.
-
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...