Parameters 435
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00 …100000.00
mH
Direct axis inductance.
1 = 10 mH
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00 …100000.00
mH
Quadrature axis inductance.
1 = 10 mH
Defines an angle offset between the zero position of the
synchronous motor and the zero position of the position
sensor.
This value is initially set by the autophasing routine when an
absolute encoder or an incremental encoder with Z-pulse is
used. The value can be fine-tuned by setting
Notes:
• The value is in electrical degrees. The electrical angle
equals the mechanical angle multiplied by the number of
motor pole pairs.
• This parameter is valid only for permanent magnet motors.
0 deg
0…360 deg
Angle offset.
1 = 1 deg
99
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while the drive is
running.
;
(
b1);
(
b2)
Asynchronous
motor
Standard squirrel cage AC induction motor (asynchronous
induction motor).
0
Permanent magnet
motor
Permanent magnet motor. Three-phase AC synchronous
motor with permanent magnet rotor and sinusoidal BackEMF
voltage.
1
SynRM
Synchronous reluctance motor. Three-phase AC synchronous
motor with salient pole rotor without permanent magnets.
2
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...