400 Parameters
Specifies the type of temperature sensor connected to
interface module 1. Note that the module must also be
activated by parameters
None
None.
0
PTC
PTC. (The unit is ohms.)
1
KTY-84
KTY84. (The unit is selected by parameter
2
Defines a filtering time for the temperature measurement
through interface module 1.
1500 ms
0…10000 ms
Filtering time for temperature measurement.
-
Specifies the type of temperature sensor connected to
interface module 2. Note that the module must also be
activated by parameters
…
None
None.
0
PTC
PTC. (The unit is ohms.)
1
KTY-84
KTY84. (The unit is selected by parameter
2
Defines a filtering time for the temperature measurement
through interface 2.
1500 ms
0…10000 ms
Filtering time for temperature measurement.
-
Selects the encoder input on interface module 1 whose signal
is echoed by or emulated to the TTL output.
See also section
(page
).
Not selected
TTL output not in use.
0
Module input 1
Input 1 is echoed by or emulated to the TTL output.
1
Module input 2
Input 2 is echoed by or emulated to the TTL output.
2
Defines the number of TTL pulses per revolution for encoder
emulation output of interface module 1.
0
0…65535
Number of TTL pulses for emulation.
1 = 1
Module 1 emulated
Z-pulse offset
With interface module 1, defines when zero pulses are
emulated in relation to zero position received from the
encoder.
For example, with a value of 0.50000, a zero pulse is
emulated whenever the encoder position passes 0.5
revolutions. With a value of 0.00000, a zero pulse is emulated
whenever the encoder position passes zero position.
0.00000
0.00000 … 1.00000
rev
Position of emulated zero pulses.
32767 =
1 rev
Selects the encoder input on interface module 2 whose signal
is echoed by or emulated to the TTL output.
See also section
(page
).
Not selected
TTL output not in use.
0
Module input 1
Input 1 is echoed by or emulated to the TTL output.
1
Module input 2
Input 2 is echoed by or emulated to the TTL output.
2
Defines the number of TTL pulses per revolution for encoder
emulation output of interface module 2.
0
0…65535
Number of TTL pulses for emulation.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...