442 Parameters
Defines the capacitance of a custom sine filter, ie. when
parameter
bit 3 is activated.
If the capacitors are star/wye-connected, enter the
capacitance of one leg into the parameter.
If the capacitors are delta-connected, multiply the capacitance
of one leg by 3 and enter the result into the parameter.
Note:
For an ABB sine filter (
bit 1),
this parameter is set automatically and should not be
adjusted.
-
0.00 … 100000.00
µF
Capacitance of custom sine filter.
100 = 1 µF
200
FSO-xx settings.
This group contains parameters related to the optional FSO-xx safety functions module. For details, refer to
the documentation of the FSO-xx module.
206
207
Distributed I/O bus settings.
These groups are only visible with a BCU control unit.
207 I/O bus service
208 I/O bus diagnostics
209 I/O bus fan
identification
These groups contain parameters related to the distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For details, refer to
CIO-01 I/O module for distributed I/O
bus control user’s manual
(3AXD50000126880 [English]).
No.
Name/Value
Description
Def
/
FbEq16
M
Sine filter
3~
Drive
C
=
C
C
C
M
Sine filter
3~
Drive
C
C
C
= 3 ×
C
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...