410 Parameters
Defines a stop delay for the supply unit. This parameter can
be used to delay the opening of the main breaker/contactor
when a restart is expected.
600.0 s
0.0 … 3600.0 s
Supply unit stop delay.
10 = 1 s
(Only visible when IGBT supply unit control activated by
)
Displays the DC voltage reference sent to the supply unit.
This parameter is read-only.
-
0.0 … 2000.0 V
DC voltage reference sent to supply unit.
10 = 1 V
(Only visible when IGBT supply unit control activated by
)
Selects the source of the DC voltage reference to be sent to
the supply unit.
Zero
None.
0
User ref
.
1
). -
(Only visible when IGBT supply unit control activated by
)
Defines the DC voltage reference for the supply unit when
is set to
.
0.0 V
0.0 … 2000.0 V
User DC reference.
10 = 1 V
(Only visible when IGBT supply unit control activated by
)
Displays the reactive power reference sent to the supply unit.
This parameter is read-only.
-
-3276.8 … 3276.7
kvar
Reactive power reference sent to the supply unit.
10 = 1 kvar
(Only visible when IGBT supply unit control activated by
)
Selects the source of the reactive power reference to be sent
to the supply unit.
Zero
None.
0
User ref
.
1
). -
(Only visible when IGBT supply unit control activated by
)
Defines the reactive power reference for the supply unit when
is set to
.
0.0 kvar
-3276.8 … 3276.7
kvar
User reactive power reference.
10 = 1 kvar
Defines the maximum shaft power for motoring mode upon a
supply network failure when IGBT supply unit control is active
(bit 15 of
is on).
The value is given in percent of nominal motor power.
Note:
With a diode supply unit (bit 11 of
is on), the
motoring shaft power is limited to 2% upon a network failure
regardless of this parameter.
600.00%
0.00 … 600.00%
Maximum shaft power for motoring mode upon a supply
network failure.
1 = 1%
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...