Fault tracing 537
FB14
Memory unit FW load
failed
The memory unit is empty, or
contains incompatible or
corrupted firmware.
Recycle the power to the control unit.
Check the sticker on the memory unit to
confirm that the firmware is compatible
with the control unit (ZCU-1x/BCU-x2).
Connect Drive composer PC tool
(version 2.3 or later) to the drive. Select
Tools - Recover drive.
If the problem persists, replace the
memory unit.
FF61
ID run
Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group
.
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that the motor shaft is not locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
0001 Maximum current limit too low.
Check settings of parameters
and
. Make sure that
>
.
Check that the drive is dimensioned
correctly according to the motor.
0002 Maximum speed limit or
calculated field weakening
point too low.
Check settings of parameters
•
•
•
•
•
Make sure that
•
> (0.55 ×
) >
(0.50 × synchronous speed)
•
< 0, and
• supply voltage > (0.66 ×
).
0003 Maximum torque limit too low.
Check settings of parameter
, and the torque limits in
group
Make sure that the maximum torque limit
in force is greater than 100%.
0004 Current measurement
calibration did not finish within
reasonable time.
Contact your local ABB representative.
0005…0008 Internal error.
Contact your local ABB representative.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
Contact your local ABB representative.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
Contact your local ABB representative.
Code
(hex)
Fault
Cause
What to do
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...