Application macros 101
Default control connections for the Hand/Auto macro
Fault
XPOW
External power input
1
+24VI
24 V DC, 2
A
2
GND
XAI
Reference voltage and analog inputs
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Speed reference (Hand)
0(2)…10 V,
R
in
> 200 kohm
5
AI1-
6
AI2+
Speed reference (Auto)
0(4)…20 mA,
R
in
= 100 ohm
7
AI2-
XAO
Analog
outputs
1
AO1
Motor speed rpm
0…20 mA,
R
L
< 500 ohm
2
AGND
3
AO2
Motor current
0…20 mA,
R
L
< 500 ohm
4
AGND
XD2D
Drive-to-drive link
1
B
Master/follower, drive-to-drive or embedded fieldbus
interface connection
2
A
3
BGND
XRO1, XRO2, XRO3
Relay outputs
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
XD24
Digital interlock
1
DIIL
Run enable
2
+24VD
+24 V DC 200 mA
3
DICOM
Digital input ground
4
+24VD
+24 V DC 200 mA
5
DIOGND Digital input/output ground
XDIO
Digital input/outputs
1
DIO1
2
DIO2
XDI
Digital inputs
1
DI1
Stop (0) / Start (1) – Hand
2
DI2
Forward (0) / Reverse (1) – Hand
3
DI3
Hand (0) / Auto (1)
4
DI4
Constant speed 1 (1 = On)
5
DI5
Forward (0) / Reverse (1) – Auto
6
DI6
Stop (0) / Start (1) – Auto
XSTO
Safe torque off circuits must be closed for the drive to start. See
Hardware manual
of drive.
X12
Safety options connection
X13
Control panel connection
X205
Memory unit connection
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...