162 Parameters
Defines the real internal value that corresponds to the
minimum analog input AI1 value defined by parameter
. (Changing the polarity settings of
and
can effectively invert the analog input.)
0.000
-32768.000 …
32767.000
Real value corresponding to minimum AI1 value.
1 = 1
Defines the real internal value that corresponds to the
maximum analog input AI1 value defined by parameter
. See the drawing at parameter
.
1500.000;
1800.000
(
b0)
-32768.000 …
32767.000
Real value corresponding to maximum AI1 value.
1 = 1
Displays the value of analog input AI2 in mA or V (depending
on whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
-
-22.000 … 22.000
mA or V
Value of analog input AI2.
1000 = 1 mA
or V
Displays the value of analog input AI2 after scaling. See
parameters
and
This parameter is read-only.
-
-32768.000 …
32767.000
Scaled value of analog input AI2.
1 = 1
Selects the unit for readings and settings related to analog
input AI2.
Note:
This setting must match the corresponding hardware
setting on the drive control unit (see the hardware manual of
the drive). Control board reboot (either by cycling the power or
through parameter
) is required to
validate any changes in the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
Defines the filter time constant for analog input AI2. See
parameter
.
0.100 s
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
No.
Name/Value
Description
Def
/
FbEq16
AI
in
(
AI
scaled
(
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...