Parameters 217
Enables/disables the critical speeds function. Also determines
whether the specified ranges are effective in both rotating
directions or not.
See also section
(page
0000b
0000b…0011b
Critical speeds configuration word.
1 = 1
Defines the low limit for critical speed range 1.
Note:
This value must be less than or equal to the value of
.
0.00 rpm
-30000.00 …
30000.00 rpm
Low limit for critical speed 1.
See par.
Defines the high limit for critical speed range 1.
Note:
This value must be greater than or equal to the value of
0.00 rpm
-30000.00 …
30000.00 rpm
High limit for critical speed 1.
See par.
Defines the low limit for critical speed range 2.
Note:
This value must be less than or equal to the value of
.
0.00 rpm
-30000.00 …
30000.00 rpm
Low limit for critical speed 2.
See par.
Defines the high limit for critical speed range 2.
Note:
This value must be greater than or equal to the value of
0.00 rpm
-30000.00 …
30000.00 rpm
High limit for critical speed 2.
See par.
Defines the low limit for critical speed range 3.
Note:
This value must be less than or equal to the value of
.
0.00 rpm
-30000.00 …
30000.00 rpm
Low limit for critical speed 3.
See par.
Defines the high limit for critical speed range 3.
Note:
This value must be greater than or equal to the value of
0.00 rpm
-30000.00 …
30000.00 rpm
High limit for critical speed 3.
See par.
Activates and selects the mode of the motor potentiometer.
See section
Disabled
Motor potentiometer is disabled and its value set to 0.
0
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
Enable
1 = Enable: Critical speeds enabled.
0 = Disable: Critical speeds disabled.
1
Sign mode
1 = Signed: The signs of parameters
are taken into
account.
0 = Absolute: Parameters
are handled as absolute values.
Each range is effective in both directions of rotation.
2…15
Reserved
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...