Parameters 371
In the D2D master, parameters
specify the mode
of follower status word monitoring. Each follower can
individually be set to be monitored continuously, or only when
it is in stopped state.
This parameter selects the mode of status word monitoring of
followers 1…16.
-
0000h…FFFFh
D2D status supervision mode selection 1.
1 = 1
Selects the mode of status word monitoring of followers
17…32.
-
0000h…FFFFh
D2D status supervision mode selection 2.
1 = 1
Defines a wake-up delay during which no master/follower
communication faults or warnings are generated. This is to
allow all drives on the master/follower link to power up.
The master cannot be started until the delay elapses or all
monitored followers are found to be ready.
60.0 s
0.0 … 180.0 s
Master/follower wake-up delay.
10 = 1 s
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Follower 1
0 = Status of follower 1 is monitored continuously.
1 = Status of follower 1 is monitored only when it is in stopped state.
1
Follower 2
0 = Status of follower 2 is monitored continuously.
1 = Status of follower 2 is monitored only when it is in stopped state.
…
…
…
15
Follower 16
0 = Status of follower 16 is monitored continuously.
1 = Status of follower 16 is monitored only when it is in stopped state.
Bit
Name
Description
0
Follower 17
0 = Status of follower 17 is monitored continuously.
1 = Status of follower 17 is monitored only when it is in stopped state.
1
Follower 18
0 = Status of follower 18 is monitored continuously.
1 = Status of follower 18 is monitored only when it is in stopped state.
…
…
…
15
Follower 32
0 = Status of follower 32 is monitored continuously.
1 = Status of follower 32 is monitored only when it is in stopped state.
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...