506 Fault tracing
A686
Checksum mismatch
Programmable warning:
The calculated parameter
checksum does not match any
enabled reference checksum.
Check that all necessary approved
(reference) checksums (
…
Check the parameter configuration.
Using
,
enable a checksum parameter and copy
the actual checksum into that parameter.
A687
Checksum
configuration
An action has been defined for
a parameter checksum
mismatch but the feature has
not been configured.
Contact your local ABB representative for
configuring the feature, or disable the
feature in
A688
Parameter map
configuration
Too much data in parameter
mapping table created in Drive
customizer.
See the
Drive customizer PC tool user’s
manual
(3AUA0000104167 [English]).
A689
Mapped parameter
value cut
Parameter value saturated eg.
by the scaling specified in
parameter mapping table
(created in Drive customizer).
Check parameter scaling and format in
parameter mapping table. See the
Drive
customizer PC tool user’s manual
(3AUA0000104167 [English]).
A6A4
Motor nominal value
The motor parameters are set
incorrectly.
Check the auxiliary code. See actions for
each code below.
The drive is not dimensioned
correctly.
1 Slip frequency is too small
Check the settings of the motor
configuration parameters in groups 98
and 99.
Check that the drive is sized correctly for
the motor.
2 Synchronous and nominal
speeds differ too much
3 Nominal speed is higher than
synchronous speed with 1 pole
pair
4 Nominal current is outside
limits
5 Nominal voltage is outside
limits
6 Nominal power is higher than
apparent power
7 Nominal power not consistent
with nominal speed and torque
A6A5
No motor data
Parameters in group 99 have
not been set.
Check that all the required parameters in
group 99 have been set.
Note:
It is normal for this warning to
appear during the start-up and continue
until the motor data is entered.
A6A6
Supply voltage
unselected
The supply voltage has not
been defined.
Set supply voltage in parameter
A6B0
User lock is open
The user lock is open, ie. user
lock configuration parameters
…
are visible.
Close the user lock by entering an invalid
pass code in parameter
(page
).
A6B1
User pass code not
confirmed
A new user pass code has
been entered in parameter
but not confirmed in
.
Confirm the new pass code by entering
the same code in
. To cancel,
close the user lock without confirming the
new code. See section
(page
).
Code
(hex)
Warning
Cause
What to do
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...