Parameters 425
Specifies an ID number for the drive. The ID can be read by
an external controller through DDCS, for example, for
comparison with an ID contained by the controller’s
application.
0
0…32767
ID number.
1 = 1
Enables/disables power-up logging. When enabled, an event
(
) is logged by the drive upon each power-up.
Disable
Power-up event logging disabled.
0
Enable
Power-up event logging enabled.
1
Clears the contents of the event logs. See section
(page
).
00000
00001
Clear the event logs. (The value will automatically revert to
00000.)
1
Displays the actual parameter configuration checksum. The
checksum is generated and updated whenever an action is
selected in
.
The parameters included in the calculation have been pre-
selected, but the selection can be edited using the Drive
customizer PC tool.
See also section
Parameter checksum calculation
0h
00000000h…
FFFFFFFFh
Actual checksum.
-
Selects how the drive reacts if the parameter checksum
(
) does not match any of the active
approved checksums (
). The active checksums
are selected by
.
No action
No action taken. (The checksum feature is not in use.)
0
Pure event
The drive generates an event log entry (
).
1
Warning
The drive generates a warning (
2
Warning and
prevent start
The drive generates a warning (
Starting the drive is prevented.
3
Fault
The drive trips on
4
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...