80 Program features
Motor thermal protection
The control program features two separate motor temperature monitoring functions.
The temperature data sources and warning/trip limits can be set up independently for
each function.
The motor temperature can be monitored using
• the motor thermal protection model (estimated temperature derived internally
inside the drive), or
• sensors installed in the windings. This will result in a more accurate motor model.
In addition to temperature monitoring, a protection function is available for ‘Ex’ motors
installed in a potentially explosive atmosphere.
Motor thermal protection model
The drive calculates the temperature of the motor on the basis of the following
assumptions:
1. When power is applied to the drive for the first time, the motor is assumed to be at
ambient temperature (defined by parameter
After this, when power is applied to the drive, the motor is assumed to be at the
estimated temperature.
2. Motor temperature is calculated using the user-adjustable motor thermal time and
motor load curve. The load curve should be adjusted in case the ambient
temperature exceeds 30 °C.
The motor thermal protection model fulfills standard IEC/EN 61800-5-1 ed. 2.1
requirements for thermal memory retention and speed sensitivity. The estimated
temperature is retained over power down. Speed dependency is set by parameters
,
and
.
Note:
The motor thermal model can be used when only one motor is connected to
the drive.
Temperature monitoring using PTC sensors
One PTC sensor can be connected to digital input DI6.
The resistance of the PTC sensor increases when its temperature rises. The
increasing resistance of the sensor decreases the voltage at the input, and eventually
its state switches from 1 to 0, indicating overtemperature.
DI6
+24VD
T
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...