Parameters 299
Defines the motor load curve together with parameters
and
.
The load curve is
used by the motor thermal protection model to estimate the
motor temperature.
When the parameter is set to 100%, the maximum load is
taken as the value of parameter
(higher loads heat up the motor). The load curve level should
be adjusted if the ambient temperature differs from the
nominal value set in
.
100%
50 … 150%
Maximum load for the motor load curve.
1 = 1%
Defines the motor load curve together with parameters
. Defines the
maximum motor load at zero speed of the load curve. A higher
value can be used if the motor has an external motor fan to
boost the cooling. See the motor manufacturer's
recommendations.
See parameter
70%
25…150%
Zero speed load for the motor load curve.
1 = 1%
Defines the motor load curve together with parameters
. Defines the
break point frequency of the load curve i.e. the point at which
the motor load curve begins to decrease from the value of
parameter
parameter
See parameter
45.00 Hz
1.00 … 500.00 Hz
Break point for the motor load curve.
See par.
No.
Name/Value
Description
Def
/
FbEq16
50
100
150
I/I
N
(%)
I
= Motor current
I
N
= Nominal motor current
Drive output
frequency
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...