Additional parameter data 471
35.13 Temperature 1 warning limit
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
°C, °F or
ohm
1 = 1 unit
35.14 Temperature 1 AI source
-
-
1 = 1
35.21 Temperature 2 source
0…11
-
1 = 1
35.22 Temperature 2 fault limit
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
°C, °F or
ohm
1 = 1 unit
35.23 Temperature 2 warning limit
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
°C, °F or
ohm
1 = 1 unit
35.24 Temperature 2 AI source
-
-
1 = 1
35.30 FPTC configuration word
0000h…FFFFh
-
1 = 1
35.50 Motor ambient temperature
-60 … 100 °C or
-76 … 212 °F
°C or °F
1 = 1°
35.51 Motor load curve
50…150
%
1 = 1%
35.52 Zero speed load
25…150
%
1 = 1%
35.53 Break point
1.00 … 500.00
Hz
100 = 1 Hz
35.54 Motor nominal temperature
rise
0…300 °C or 32…572 °F
°C or °F
1 = 1°
35.55 Motor thermal time constant
100…10000
s
1 = 1 s
35.56 Motor overload action
0…2
-
1 = 1
35.57 Motor overload class
0…4
-
1 = 1
35.60 Cable temperature
0.0 … 200.0
%
10 = 1%
35.61 Cable nominal current
0.00 … 10000.0
A
100 = 1 A
35.62 Cable thermal rise time
0…50000
s
1 = 1 s
35.100 DOL starter control source
-
-
1 = 1
35.101 DOL starter on delay
0…42949673
s
1 = 1 s
35.102 DOL starter off delay
0…715828
min
1 = 1 min
35.103 DOL starter feedback source
-
-
1 = 1
35.104 DOL starter feedback delay
0…42949673
s
1 = 1 s
35.105 DOL starter status word
0000b…1111b
-
1 = 1
35.106 DOL starter event type
0…2
-
1 = 1
36 Load analyzer
36.01 PVL signal source
-
-
1 = 1
36.02 PVL filter time
0.00 … 120.00
s
100 = 1 s
36.06 AL2 signal source
-
-
1 = 1
36.07 AL2 signal scaling
0.00 … 32767.00
-
100 = 1
36.08 Logger function
00b…11b
-
1 = 1
36.09 Reset loggers
0…3
-
1 = 1
36.10 PVL peak value
-32768.00 … 32767.00
-
100 = 1
36.11 PVL peak date
-
-
1 = 1
36.12 PVL peak time
-
-
1 = 1
36.13 PVL current at peak
-32768.00 … 32767.00
A
100 = 1 A
No.
Name
Type
Range
Unit
FbEq32
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...