Parameters 281
Sets a custom motor current fault limit.
The drive automatically sets an internal motor current limit
according to the drive hardware. The internal limit is
appropriate in most cases, but this parameter can be used to
set a lower current limit, for example, to protect a permanent
magnet motor from demagnetization.
Note:
The limit defines the maximum peak current of one
phase.
With this parameter at 0.0 A, only the internal limit is in force.
0.00 A
0.00 … 30000.00 A Custom motor current fault limit.
See par.
Selects the stop mode when a non-critical fault occurs.
Coast
The drive coasts to a stop.
0
Emergency ramp
The drive follows the ramp specified for an emergency stop in
parameter
1
Selects how the drive reacts when the communication to an
I/O extension module fails.
No action
No action taken.
0
Warning
The drive generates a warning,
1
Fault
.
2
(Only visible when IGBT supply unit control activated by
)
Selects how the supply unit reacts when an earth fault or
current unbalance is detected.
No action
No action taken.
0
Warning
The supply unit generates a warning,
.
1
Fault
The supply unit trips on a fault,
2
(Only visible when IGBT supply unit control activated by
)
Selects how the supply unit reacts when a supply phase loss
is detected.
No action
No action taken.
0
Fault
The supply unit trips on a fault,
.
1
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...