134 Parameters
Start inhibit status word. This word specifies the source of the
inhibiting condition that is preventing the drive from starting.
After the condition is removed, the start command must be
cycled. See bit-specific notes.
See also parameter
, and
, bit 1.
This parameter is read-only.
-
0000h…FFFFh
Start inhibit status word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
Note
0
Not ready run
1 = DC voltage is missing or drive has not been parametrized
correctly. Check the parameters in groups
.
a
1
Ctrl location
changed
1 = Control location has changed
a,c
2
SSW inhibit
1 = Control program is keeping itself in inhibited state
a
3
Fault
1 = A fault is active
a,c
4
Lost start enable
1 = Start enable signal missing
a
5
Lost run enable
1 = Run enable signal missing
a
6
FSO inhibit
1 = Operation prevented by FSO-xx safety functions module b
7
STO
1 = Safe torque off active
b
8
Current calibration
ended
1 = Current calibration routine has finished
b,c
9
ID run ended
1 = Motor identification run has finished
b,c
10
Auto phase ended 1 = Autophasing routine has finished
b,c
11
Em Off1
1 = Emergency stop signal (mode Off1)
b
12
Em Off2
1 = Emergency stop signal (mode Off2)
b
13
Em Off3
1 = Emergency stop signal (mode Off3)
b
14
Auto reset inhibit 1 = The autoreset function is inhibiting operation
15
Jogging active
1 = The jogging enable signal is inhibiting operation
b
Notes:
a
is still set after the removal of the inhibiting condition,
and edge triggering is selected for the active external control location, a fresh rising-edge
start signal is required. See parameters
.
b
is still set after the removal of the inhibiting condition, a
fresh rising-edge start signal is required.
c
Informative bit. The inhibiting condition need not be removed by the user.
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...