202 Parameters
DIIL
DIIL input (
, bit 15).
33
Active control
source MCW bit 3
Control word bit 3 received from the active control source.
Notes:
• If the drive is running in fieldbus control, switching bit 3 off
effectively removes both the start and run enable signals.
In this case, the stop mode is determined by either
or
, whichever
mode has higher priority. The order of stop modes from
highest to lowest priority is
• In case the active source is the control panel, PC tool or
drive I/O, the run enable signal is always on.
34
). -
Selects the source for the start enable signal.
1 = Start enable.
With the signal switched off, any drive start command is
inhibited. (Switching the signal off while the drive is running
will not stop the drive.)
Notes:
• If a level-triggered start command is on when the start
enable signal switches on, the drive will start. (An edge-
triggered start signal must be cycled for the drive to start.)
See parameters
and
.
• The warning that indicates a missing signal can be
suppressed using parameter
.
.
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
DIIL
DIIL input (
, bit 15).
30
). -
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...