Fieldbus control through the embedded fieldbus interface (EFB) 559
References
The ABB drives profile supports the use of two references, EFB reference 1 and EFB
reference 2. The references are 16-bit words each containing a sign bit and a 15-bit
integer. A negative reference is formed by calculating the two’s complement from the
corresponding positive reference.
The references are scaled as defined by parameters
…
; which scaling is
in use depends on the setting of
and
(see
page
).
The scaled references are shown by parameters
.
(with speed reference)
(with frequency reference)
0
-20000
20000
Drive
Fieldbus
0 (with torque or power reference)
±(
) (with speed reference)
) (with frequency reference)
10000
-10000
(with torque reference)
(with power reference)
-(
) (with speed reference)
-(
) (with frequency reference)
-(
) (with torque reference)
-(
) (with power reference)