Parameters 221
Defines acceleration time 1 as the time required for the speed
to change from zero to the speed defined by parameter
(
not
to parameter
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the acceleration
rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
20.000 s
0.000 …1800.000 s Acceleration time 1.
10 = 1 s
Defines deceleration time 1 as the time required for the speed
to change from the speed defined by parameter
not
from parameter
) to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the reference.
If the reference changes faster than the set deceleration rate,
the motor speed will follow the deceleration rate.
If the deceleration rate is set too short, the drive will
automatically prolong the deceleration in order not to exceed
drive torque limits (or not to exceed a safe DC link voltage). If
there is any doubt about the deceleration time being too short,
ensure that DC overvoltage control is on (parameter
Note:
If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
20.000 s
0.000 …1800.000 s Deceleration time 1.
10 = 1 s
Defines acceleration time 2. See parameter
.
60.000 s
0.000 …1800.000 s Acceleration time 2.
10 = 1 s
Defines deceleration time 2. See parameter
60.000 s
0.000 …1800.000 s Deceleration time 2.
10 = 1 s
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...