266 Parameters
Selects a source that switches between two different
predefined minimum torque limits.
0 = Minimum torque limit defined by
is active
1 = Minimum torque limit selected by
is active
The user can define two sets of torque limits, and switch
between the sets using a binary source such as a digital input.
The minimum limit selection (
) is independent of the
maximum limit selection (
).
The first set of limits is defined by parameters
. The second set has selector parameters for both the
minimum (
) and maximum (
) limits that allows the
use of a selectable analog source (such as an analog input).
The limit selection parameters are updated on a 10 ms time
level.
Note:
In addition to the user-defined limits, torque may be
limited for other reasons (such as power limitation). Refer to
the block diagram on page
.
Minimum torque 1
0 (minimum torque limit defined by
is active).
0
Minimum torque 2
source
1 (minimum torque limit selected by
is active).
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
). -
No.
Name/Value
Description
Def
/
FbEq16
User-defined
minimum torque
limit
0
AI1
AI2
PID
0
AI1
AI2
PID
0
1
0
1
User-defined
maximum torque
limit
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...