Parameters 357
Defines the node address of the drive on the fieldbus link.
Values 1…247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
1
0…255
Node address (values 1…247 are allowable).
1 = 1
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
9.6 kbps
9.6 kbit/s.
2
19.2 kbps
19.2 kbit/s.
3
38.4 kbps
38.4 kbit/s.
4
57.6 kbps
57.6 kbit/s.
5
76.8 kbps
76.8 kbit/s.
6
115.2 kbps
115.2 kbit/s.
7
Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
8 NONE 1
Eight data bits, no parity bit, one stop bit.
0
8 NONE 2
Eight data bits, no parity bit, two stop bits.
1
8 EVEN 1
Eight data bits, even parity bit, one stop bit.
2
8 ODD 1
Eight data bits, odd parity bit, one stop bit.
3
Validates any changes in the EFB settings, or activates silent
mode.
Enabled
Normal operation.
0
Refresh settings
Validates any changed EFB configuration settings. Reverts
automatically to
.
1
Silent mode
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
selection of this parameter.
2
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...