416 Parameters
Specifies hardware-related options that require differentiated
parameter defaults. Activating a bit in this parameter makes
the necessary changes in other parameters – for example,
activating an emergency stop option reserves a digital input.
In many cases, the differentiated parameters will also be
write-protected.
This parameter, as well as the changes in other parameters
implemented by it, are not affected by a parameter restore.
WARNING!
After switching any bits in this word,
recheck the values of the affected parameters.
Note:
This parameter cannot be changed while the drive is
running.
-
0000h…FFFFh
Hardware options configuration word 1.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
Supply frequency
60 Hz
0 = 50 Hz; 1 = 60 Hz. Affects parameters
.
1
Emergency stop
Cat 0
1 = Emergency stop, Category 0, without FSO module. Affects
.
2
Emergency stop
Cat 1
1 = Emergency stop, Category 1, without FSO module. Affects
,
3
RO2 for -07
cabinet cooling fan
1 = Control of cabinet cooling fan (used only with specific
ACS880-07 hardware). Affects
,
4
Externally powered
control unit
1 = Control unit powered externally. Affects
.
(Only visible with
a ZCU control unit)
5
DC supply switch
1 = DC switch monitoring active. Affects
.
(Only
visible with a ZCU control unit)
6
DOL motor switch 1 = Motor fan control active. Affects
.
7
xSFC-01 fuse
switch controller
1 = xSFC charging controller used. Affects
.
(Only visible with a
BCU control unit)
8
Service switch or
PTC/Pt100 relay
1 = Service switch or PTC/Pt100 relay connected. Affects
,
.
9
Output contactor
1 = Output contactor present. Affects
10
Brake resistor, sine
filter, IP54 fan
1 = Status (eg. thermal) switches connected to DIIL input. Affects
.
11
INU-DSU
communication
*1 = Diode supply unit control by inverter unit active. Makes several
parameters visible in groups
and
.
(Only visible with
a BCU control unit)
12
Reserved
13
du/dt filter
activation
1 = Active: An external du/dt filter is connected to the drive output.
The setting will limit the output switching frequency. With inverter
module frame sizes R5i to R7i, the fan of the module will be forced to
full speed.
Note:
This bit is to be left at 0 if the drive/inverter module
is equipped with internal du/dt filtering (for example, frame R8i
inverter modules with E205).
14
DOL fan activation 1 = The inverter unit consists of frame R8i modules with direct-on-
line cooling fans (C188). Disables fan feedback monitoring
and changes fan control to ON/OFF type.
15
INU-ISU
communication
*1 = IGBT supply unit control by inverter unit active. Affects
and
. Makes several parameters visible in groups
,
,
*See section
Control of a supply unit (LSU)
(page
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...