Parameters 277
Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
• The drive exceeds the stall current limit (
, and
• the output frequency is below the level set by parameter
or the motor speed is below the
, and
• the conditions above have been true longer than the time
set by parameter
.
No action
None (stall supervision disabled).
0
Warning
warning.
1
Fault
The drive trips on fault
2
Stall current limit in percent of the nominal current of the
motor. See parameter
200.0%
0.0 … 1600.0%
Stall current limit.
10 = 1%
Stall speed limit in rpm. See parameter
150.00 rpm;
180.00 rpm
(
b0)
0.00 … 10000.00
rpm
Stall speed limit.
See par.
Stall frequency limit. See parameter
.
Note:
Setting the limit below 10 Hz is not recommended.
15.00 Hz;
18.00 Hz
(
b0)
0.00 … 500.00 Hz
Stall frequency limit.
See par.
.
20 s
0 … 3600 s
Stall time.
1 = 1 s
No.
Name/Value
Description
Def
/
FbEq16