Parameters 319
Defines the minimum limit for the process PID controller
output. Using the minimum and maximum limits, it is possible
to restrict the operation range.
0.0
-32768.0 …
32767.0
Minimum limit for process PID controller output.
1 = 1
Defines the maximum limit for the process PID controller
output. See parameter
.
1500.0;
1800.0
(
b0)
-32768.0 …
32767.0
Maximum limit for process PID controller output.
1 = 1
Freezes (or defines a source that can be used to freeze) the
output of the process PID controller, keeping the output at the
value it was before freeze was enabled. This feature can be
used when, for example, a sensor providing process feedback
must to be serviced without stopping the process.
1 = Process PID controller output frozen
See also parameter
Not selected
Process PID controller output not frozen.
0
Selected
Process PID controller output frozen.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
Source selection (see
). -
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...