Parameters 419
Pass codes can be entered into this parameter to activate
further access levels (see parameter
) or to configure the user lock.
Entering “358” toggles the parameter lock, which prevents the
changing of all other parameters through the control panel or
the Drive composer PC tool.
Entering the user pass code (by default, “10000000”) enables
parameters
, which can be used to define a
new user pass code and to select the actions that are to be
prevented.
Entering an invalid pass code will close the user lock if open,
ie. hide parameters
…
. After entering the code,
check that the parameters are in fact hidden. If they are not,
enter another (random) pass code.
Entering several invalid pass codes introduces a delay before
a new attempt can be made. Entering further invalid codes will
progressively lengthen the delay.
Note:
You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in a safe
place – the protection cannot be disabled even by ABB if the
code is lost.
See also section
(page
0
0…99999999
Pass code.
-
Shows which access levels have been activated by pass
codes entered into parameter
This parameter is read-only.
0001h
0000h…FFFFh
Active access levels.
-
Selects the application macro. See chapter
(page
) for more information.
After a selection is made, the parameter reverts automatically
to
.
Note:
This parameter cannot be changed while the drive is
running.
Done
Macro selection complete; normal operation.
0
Factory
Factory macro (see page
).
1
Hand/Auto
Hand/Auto macro (see page
2
PID-CTRL
PID control macro (see page
).
3
T-CTRL
Torque control macro (see page
4
Sequence control
Sequential control macro (see page
5
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
0
End user
1
Service
2
Advanced programmer
3…10
Reserved
11
OEM access level 1
12
OEM access level 2
13
OEM access level 3
14
Parameter lock
15
Reserved
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...