Using via Digital Data Communication
------------------------------------------------------------------------------------
82
[SOURce]:RESistance[:LEVel][:IMMediate][:AMPLitude]
:Sets Internal Resistance
Function:Sets the internal resistance
Format:[SOURce]:RESistance[:LEVel][:IMMediate][:AMPLitude] <NRf>
Type:SET command, QUERY command
Parameters:Range varies on the model and the number of parallel connected devices
Response:Same as parameters
Internal Resistance(Ω) Ranges
Model(Type)
No. of
Parallel
Connected Devices
400HA
800HA
1600HA
1(Idependent Operation)
0.0~128.0
0.0~64.0
0.0~32.0
2
0.0~64.0
0.0~32.0
0.0~16.0
3
0.0~42.7
0.0~21.3
0.0~10.7
4
0.0~32.0
0.0~16.0
0.0~8.0
5
0.0~25.6
0.0~12.8
0.00~6.40
6
0.0~21.3
0.0~10.7
0.00~5.33
7
0.0~18.3
0.00~9.14
0.00~4.57
8
0.0~16.0
0.00~8.00
0.00~4.00
9
0.0~14.2
0.00~7.11
0.00~3.56
10
0.0~12.8
0.00~6.40
0.00~3.20
Restrictions: Alarm response is returned for normal SET commands in the following conditions
・If analog option is not attached (Model which A is not attached to end of name)
・While operating as a series operation slave unit
・While operating as a parallel operation slave unit
・Sequence operation in progress
<Ex.>
ZX-S-400HA(Idependent Operation)
RES 128
RES?
128.0
Summary of Contents for ZX-S-H Series
Page 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual ...
Page 37: ...Basic Operations 33 This is blank page ...
Page 59: ...Useful Function 55 This is blank page ...
Page 115: ...Using via Digital Data Communication 111 This is blank page ...
Page 141: ...Controlling with External Analog Contact Signals 137 This is blank page ...
Page 147: ...Special Loads 143 This is blank page 守 ...
Page 188: ... 184 付録 External Diagrams ZX S 400H 400HA 4 M3 ...
Page 189: ...Appendix 185 ZX S 800H 800HA ...
Page 190: ...Appendix 186 ZX S 1600H 1600HA ...