Using via Digital Data Communication
------------------------------------------------------------------------------------
104
LC
:Sets OCP Current
Function:Sets the OCP current
Format:OCP* *:Set value within range
Range:Values other than ranges result in parameter errors.
Range varies on the model and number of parallel connected devices.
OCP Current Range
Model(Type)
No. of
Parallel
Connected Devices
400H/HA
800H/HA
1600H/HA
1(Idependent Operation)
0.1~5.5
0.2~11.0
0.4~22.0
2
0.2~11.0
0.4~22.0
0.8~44.0
3
0.3~16.5
0.6~33.0
1.2~66.0
4
0.4~22.0
0.8~44.0
1.6~88.0
5
0.5~27.5
1.0~55.0
2.0~110.0
6
0.6~33.0
1.2~66.0
2.4~132.0
7
0.7~38.5
1.4~77.0
2.8~154.0
8
0.8~44.0
1.6~88.0
3.2~176.0
9
0.9~49.5
1.8~99.0
3.6~198.0
10
1.0~55.0
2.0~110.0
4.0~220.0
<Ex.>A1,LC5.5
LV
:Sets OVP Voltage
Function:Sets the OVP voltage
Format:OVP* *:Set value within range
Range:10~704
Values other than ranges will result in parameter errors.
<Ex.>A1,LV704
Summary of Contents for ZX-S-H Series
Page 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual ...
Page 37: ...Basic Operations 33 This is blank page ...
Page 59: ...Useful Function 55 This is blank page ...
Page 115: ...Using via Digital Data Communication 111 This is blank page ...
Page 141: ...Controlling with External Analog Contact Signals 137 This is blank page ...
Page 147: ...Special Loads 143 This is blank page 守 ...
Page 188: ... 184 付録 External Diagrams ZX S 400H 400HA 4 M3 ...
Page 189: ...Appendix 185 ZX S 800H 800HA ...
Page 190: ...Appendix 186 ZX S 1600H 1600HA ...