Using via Digital Data Communication
------------------------------------------------------------------------------------
94
SYSTem:SINK
:Sets SINK ON/OFF
Function: Sets the SINK function ON/OFF
Same settings as FUNCTION Settings Item 1
Format:SYSTem:SINK <String>
Type:SET command, QUERY command
Parameters: ON ・・・SINK ON
OFF ・・・SINK OFF
Response:Same as parameters
Restrictions: Alarm response is returned for normal SET commands in the following conditions
・While operating as a series operation slave unit
・While operating as a parallel operation slave unit
・
Sequence operation in progress
<Ex.>
SYST:SINK ON
SYST:SINK?
ON
SYSTem:TRIP
:Executes TRIP
Function:Executes input power relay TRIP
Format:SYSTem:TRIP
Type:SET command only
Parameters: None
<Ex.>
SYST:TRIP
This command can only be used for 1600W models.
This is valid for 400W and 800W models. However nothing will happen if executed.