Using via Digital Data Communication
------------------------------------------------------------------------------------
103
SET Commands
This section explains the SET commands of EX based commands.
A
:Assigns Device Address
Function:Assigns the device address for ZX power supplies
Format:A* *:Set value within range
Range:0~50
Assigned Address 0 is a global address. Assign addresses to all multi-connected ZX-S Series power
supplies.
Once the global address is assigned, only Output ON/OFF Toggle SET command “OT” is valid.
Further, no Acknowledge Responses will be sent only while the global address is assigned
<Ex.>A1 /* Assigns address 1 to ZX power supply */
<Ex.>A1,OT1,A2,OT1 /* Errors due multple address assignment commands */
AR
:Executes Alarm Reset
Function:Executes alarm reset (cancels triggered OVP/OCP alarms)
Format:AR* *:Set value
Set value:
1:Resets alarms
Values other than 0 and 1 result in parameter errors. (0 does nothing)
<Ex.>A1,AR1
CL
:Resets Set Parameters
Function:Resest the set parameters
Format:CL* *:Set value
Set Value:
1:Resest to factory default settings
Values other than 0 and 1 result in parameter errors. (0 does nothing)
<Ex.>A1,CL1
Do not set redundant ZX power supply addresses within the same system.
Further, only one address can be assigned per send. Assigning multiple addresses at once is not
possible.
Caution
Execute alarm reset only once cause has been resolved.
Caution
Summary of Contents for ZX-S-H Series
Page 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual ...
Page 37: ...Basic Operations 33 This is blank page ...
Page 59: ...Useful Function 55 This is blank page ...
Page 115: ...Using via Digital Data Communication 111 This is blank page ...
Page 141: ...Controlling with External Analog Contact Signals 137 This is blank page ...
Page 147: ...Special Loads 143 This is blank page 守 ...
Page 188: ... 184 付録 External Diagrams ZX S 400H 400HA 4 M3 ...
Page 189: ...Appendix 185 ZX S 800H 800HA ...
Page 190: ...Appendix 186 ZX S 1600H 1600HA ...