background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8359  Rev.5  P. 1 / 2

INSTRUCTION MANUAL

POWER SUPPLY MODULE

(single slot, continuous output current 750 mA)

MODEL

R3-PS1

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Power supply module ..........................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  85 – 132V AC rating: 85 – 132V, 47 – 66 Hz, approx. 45VA
  170 – 264V AC rating: 170 – 264V, 47 – 66 Hz, approx. 45VA
  24V DC rating: 24V ±10%, approx. 29W or 1.2A at 24V
  110V DC rating: 85 – 150V, approx. 29W or 270mA at 110V

 

GENERAL PRECAUTIONS

• Before you remove the unit from its base or mount it, turn 

off the power supply for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base (model: R3-BSx).
For heat dissipation, install the power supply module into 
the rightmost slot or leftmost slot.  For redundant power 
system, install two modules in series into the rightmost slot 
or leftmost slot.  If there is no problem, the rightmost slot 
is recommended.
In case of redundant power system use, be sure to install 
two same current capacity power supply modules (model: 
R3-PS1) in series.  The combination of different current ca-
pacity power supply module or interface module with power 
supply is not available.

COMPONENT IDENTIFICATION

 

FRONT VIEW

1

2

3

4

5

6

Power LED

Power LED

:  Green LED turns on when the power is sup-

plied.

Reviews: