5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8359 Rev.5 P. 1 / 2
INSTRUCTION MANUAL
POWER SUPPLY MODULE
(single slot, continuous output current 750 mA)
MODEL
R3-PS1
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■
PACKAGE INCLUDES:
Power supply module ..........................................................(1)
■
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■
CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■
POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
85 – 132V AC rating: 85 – 132V, 47 – 66 Hz, approx. 45VA
170 – 264V AC rating: 170 – 264V, 47 – 66 Hz, approx. 45VA
24V DC rating: 24V ±10%, approx. 29W or 1.2A at 24V
110V DC rating: 85 – 150V, approx. 29W or 270mA at 110V
■
GENERAL PRECAUTIONS
• Before you remove the unit from its base or mount it, turn
off the power supply for safety.
■
ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■
WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■
AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
For heat dissipation, install the power supply module into
the rightmost slot or leftmost slot. For redundant power
system, install two modules in series into the rightmost slot
or leftmost slot. If there is no problem, the rightmost slot
is recommended.
In case of redundant power system use, be sure to install
two same current capacity power supply modules (model:
R3-PS1) in series. The combination of different current ca-
pacity power supply module or interface module with power
supply is not available.
COMPONENT IDENTIFICATION
■
FRONT VIEW
1
2
3
4
5
6
Power LED
Power LED
: Green LED turns on when the power is sup-
plied.