background image

R3-PS1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8359  Rev.5  P. 2 / 2

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

1

2

3

4

5

6

130 (5.1

2)

27.5 (1.08)

109 (4.29)

POSITIONING

GUIDE

TERMINAL

COVER

6-M3

SCREW

6.2

(.24)

 

CONNECTION DIAGRAM

INTERNAL 

POWER

2

3

6

U (+) 

V (–) 

FG

POWER INPUT

BUS CONNECTOR

1

4

RUN 

+

RUN 

RUN CONTACT

OUTPUT

*

1

*

1. RUN contact is available with Ver.1.01 or higher versions.

*

2. In order to improve EMC performance, bond the FG terminal 

     to the ground.
Caution: This terminal is NOT a protective conductor terminal.

*

2

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.75 – 1.25 mm

2

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd., Nichifu Co., Ltd.

12max

6max

3max

4min

3.2 dia.

(mm)