8 - 12
8. ETHERNET CONNECTION
8.2 System Configuration
8.2.2
Connection to Built-in Ethernet port CPU or C Controller module
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver, or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standard.
*2
A straight cable is available.
When connecting QnUDE(H) and GOT directly with Ethernet cable, connection by cross cable is available.
Ethernet(MELSEC),Q17nNC,CRnD-700
Communication driver
Connecting to
Built-in
Ethernet port
CPU
GOT
Connection cable
PLC
Connection cable
*1*2
Maximum
segment
length
*4
GOT
Number of
connectable
equipment
Model name
Communication
type
Option device
Model
MELSEC iQ-R
Series
*10*11
Ethernet
Twisted pair cable
• 10BASE-T
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP):
Category 3, 4, and 5
• 100BASE-TX
Shielded twisted pair cable (STP):
Category 5 and 5e
100m
- (Built into GOT)
*3
*9
16 GOTs
Motion controller
CPU
*10*11
(MELSEC iQ-R
Series)
Ethernet
C Controller module
(MELSEC iQ-R
Series)
Ethernet
MELSEC-QnUDE(H)
*5*6
MELSEC-QnUDV
*5*6
Ethernet
- (Built into GOT)
*3
*9
GT15-J71E71-100
C Controller module
(Q Series)
Ethernet
100m
- (Built into GOT)
*3
*9
*14
GT15-J71E71-100
MELSEC-L
*7*8
Ethernet
100m
- (Built into GOT)
*3
*9
16 GOTs
GT15-J71E71-100
MELSEC-FX
(FX
3GE
)
Ethernet
100m
- (Built into GOT)
*3
*9
4 GOTs
GT15-J71E71-100
MELSEC iQ-F
Series
*12*13
Ethernet
Twisted pair cable
• 10BASE-T
Shielded twisted pair cable (STP):
Category 3 or higher
• 100BASE-TX
Shielded twisted pair cable (STP):
Category 5 or higher
100m
- (Built into GOT)
*3
*9
8 GOTs
Summary of Contents for GT15
Page 2: ......
Page 34: ...A 32 ...
Page 92: ......
Page 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Page 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Page 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Page 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Page 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Page 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Page 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Page 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Page 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Page 510: ......
Page 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Page 668: ......
Page 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Page 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Page 714: ......
Page 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Page 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Page 762: ......
Page 860: ...REVISIONS 4 ...
Page 863: ......