15 - 36
15. INVERTER CONNECTION
15.5 FREQROL Series Inverter Side Settings
15.5.3 Connecting FREQROL-F500, F500L series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit). Set Pr.160 (user group read selection) to 0 [All
parameters can be accessed for reading and writing.] before making the parameter settings.
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual of FREQROL-F500 and F500L series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
*5
There is no Protocol selection setting on the inverter side.
*6
The setting is required on the inverter side when FR-A5NR is used.
GOT connection destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124
FR-A5NR (Option unit)
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342
Setting item
*1
Parameter No.
Set value
Contents of setting
PU connector
FR-A5NR
Communication station number
Pr.117
Pr.331
0 to 31
Communication speed
*2
Pr.118
Pr.332
192
*4
19200bps
Stop bit length/data length
Stop bit length
*2
Pr.119
Pr.333
10
Data length: 7bit
Stop bit length: 1bit
Parity check presence/absence
*2
Pr.120
Pr.334
1
Odd
Number of communication retries
Pr.121
Pr.335
9999
The inverter will not come to an
alarm stop.
Communication check time interval
Pr.122
Pr.336
9999
Communication check
suspension
Wait time setting
Pr.123
Pr.337
0
0ms
CRLF presence/ absence selection
Pr.124
Pr.341
1
*3
With CR, without LF
Protocol selection
*5
―
―
―
―
Operation mode selection
Pr.79
PU
connector
1
PU operation mode
FR-A5NR
0
*3
External operation mode at
power on
Link start mode selection
*6
―
Pr.340
1
Computer link operation
E
2
PROM write selection
*6
―
Pr.342
0
*3
Written to RAM and EEPROM
Summary of Contents for GT15
Page 2: ......
Page 34: ...A 32 ...
Page 92: ......
Page 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Page 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Page 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Page 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Page 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Page 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Page 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Page 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Page 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Page 510: ......
Page 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Page 668: ......
Page 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Page 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Page 714: ......
Page 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Page 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Page 762: ......
Page 860: ...REVISIONS 4 ...
Page 863: ......