13 - 38
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
(b) Station information setting
: Necessary : As necessary : Not necessary
*1
Specify the same number of occupied stations as that of the
GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
(2) Setting from sequence program
The parameter is written to the buffer memory, and the
data link is automatically started when PLC CPU status
changes from STOP to RUN.
(a) I/O signal of CC-Link module
Control & Communication Link System Master/
Local Module Type AJ61QBT11/A1SJ61QBT11
User's Manual
(b) Device used by user
(c) Buffer memory settings used in the present
example
*1
Details for the station data are shown below.
For 1) and 2), set the same station No. and number of station
occupied as those of the GOT.
For 3), the setting is fixed.
Item
Set value
Setting
necessity at
GOT
connection
Station type
Intelligent device station
(fixed)
Exclusive station count
*1
Exclusive station 1
Reserve/invalid station
select
No setting
Intelligent buffer select
(word)
(Use default value)
Device
Application
M100, M101
Flag for parameter setting
M102, M103
Flag for data link startup
D0
Number of connected modules
D1
Number of retry
D2
Automatic reconnection station count
D3
Operation specification in the case of CPU failure
D4
Reserved station specification (Station No. 1 to
Station No. 16)
D5
Error invalid station specification (Station No. 1 to
Station No. 16)
D6
Station data (first module)
D400
Error code in the case of data link startup failure
Buffer memory
address
Item
Set value
Decimal (Hex)
1(11 (1
H
)
Number of connected modules
1 (1 module)
2(22 (2
H
)
Number of retry
3 (3times)
3(33 (3
H
)
Automatic reconnection station
count
1 (1 station)
6(66 (6
H
)
Operation specification in the
case of CPU failure
0 (stop)
16(1016 (10
H
)
Reserved station specification
(Station No. 1 to Station No. 16)
0 (No
specification)
20(1420 (14
H
)
Error invalid station specification
(Station No. 1 to Station No. 16)
0 (No
specification)
32(2032 (20
H
)
Station data (first module)
*1
2101
H
1) Station No. (Set the same station No. as that of the GOT)
01
H
to 40
H
: Station No. 1 to Station No. 64
2) Number of stations occupied (Set the number of station
occupied as that of the GOT)
1
H
: Exclusive station 1
2
H
: Exclusive station 2
3
H
: Exclusive station 3
4
H
: Exclusive station 4
3) Station type (2
H
: Set it to intelligent device station)
0
H
: Remote I/O station
1
H
: Remote device station
2
H
: Intelligent device station (Incl. local station)
3)
2)
1)
b15
b12 b11
b8 b7
to
b0
to
to
Summary of Contents for GT15
Page 2: ......
Page 34: ...A 32 ...
Page 92: ......
Page 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Page 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Page 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Page 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Page 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Page 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Page 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Page 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Page 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Page 510: ......
Page 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Page 668: ......
Page 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Page 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Page 714: ......
Page 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Page 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Page 762: ......
Page 860: ...REVISIONS 4 ...
Page 863: ......