15 - 44
15. INVERTER CONNECTION
15.5 FREQROL Series Inverter Side Settings
15.5.10 Connecting FREQROL-A700 series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit).
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual of FREQROL-A700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
GOT connection
destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342
RS-485 terminal
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342, Pr.549
Setting item
*1
Parameter No.
Set value
Contents of setting
PU connector
RS-485
PU communication station number/RS-485
communication station number
Pr.117
Pr.331
0 to 31
PU communication speed/RS-485
communication speed
*2
Pr.118
Pr.332
192
*4
19200bps
PU communication stop bit length/
RS-485 communication stop bit length
*2
Pr.119
Pr.333
10
Data length: 7bit
Stop bit length: 1bit
PU communication parity check/
RS-485 communication parity check
*2
Pr.120
Pr.334
1
Odd
Number of PU communication retries/
RS-485 communication retry count
Pr.121
Pr.335
9999
The inverter will not come to an
alarm stop.
PU communication check time interval/
RS-485 communication check time interval
Pr.122
Pr.336
9999
*4
Communication check
suspension
PU communication waiting time setting/
RS-485 communication waiting time setting
Pr.123
Pr.337
0
0ms
PU communication CR/LF selection/
RS-485 communication CR/LF selection
Pr.124
Pr.341
1
*3
With CR, without LF
Protocol selection
―
Pr.549
0
*3
Mitsubishi Electric inverter
protocol
Operation mode selection
Pr.79
PU
connector
1
PU operation mode
RS-485
0
*3
External operation mode at
power on
Communication startup mode selection
Pr.340
PU
connector
0
*3
Refer to Pr.79 settings.
RS-485
1
Network operation mode.
Communication EEPROM write selection
Pr.342
0
*3
Written to RAM and EEPROM
Summary of Contents for GT15
Page 2: ......
Page 34: ...A 32 ...
Page 92: ......
Page 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Page 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Page 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Page 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Page 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Page 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Page 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Page 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Page 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Page 510: ......
Page 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Page 668: ......
Page 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Page 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Page 714: ......
Page 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Page 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Page 762: ......
Page 860: ...REVISIONS 4 ...
Page 863: ......