20 - 28
20. GOT MULTI-DROP CONNECTION
20.6 Setting of Serial Multi-Drop Connection Unit
(2) Assignment contents of the PLC side word device
The following table shows the device assignment
contents when setting [Head Device (10 Points)] to
"D0".
(3) Details on the word device assignment contents
(a) Control signal 1-1
< 10 second cycle flicker signal
*1
>
By the repetition of turning ON/OFF every 5
seconds, the connection between GT01-RS4-M
and the PLC can be confirmed on the PLC side.
When no repetition of this ON/OFF is observed,
GT01-RS4-M is not connected to the PLC.
*1
When writing or clearing data on the program area from the
personal computer to the PLC using FA transparent function,
flicker of the signal as shown above may be temporarily
stopped.
(b) Station information notification signal
*2
This signal notifies the status of the slave station
(GOT) which is connected to the master station
(GT01-RS4-M). Only the bit corresponding to the
number of connected slave station (GOT) is turned
ON and other bits are turned OFF.
• 1: Connected
• 0: Unconnected (Including communication error
status)
*2
When the communication between GT01-RS4-M and the
PLC becomes faulty, the station information notification
signal is not updated.
(c) Slave station control signal
This signal controls slave stations which are not
updated by the master station.
Usually, the master station accesses all stations
(up to 16 stations). In addition, if stations are
temporarily in communication error due to a power
disconnection or screen data transfer during the
steady operation, the automatic recovery of the
station is executed for one station per ten seconds.
Therefore, the automatic recovery may take
maximum 2 minutes and 30 seconds.
Using this control signal, the number of slave
stations to be monitored by the master station can
be reduced to the actual number of slave stations
to be used by a user. This makes the automatic
recovery processing smooth. If an error occurs in
only one station, the time for the station to recover
automatically can be reduced within 10 seconds.
When the bits are off and the master station and
the slave stations are in communication, the
communication with the corresponding slave
stations is disconnected if the above corresponding
bits are turned on.
Device
Description
D0 (Head 0)
Control signal 1-1
D1(Head 1)
Station information notification signal
D2(Head 2)
(Reserve)
D3(Head 3)
(Reserve)
D4(Head 4)
(Reserve)
D5(Head 5)
Slave station control signal
D6(Head 6)
(Reserve)
D7(Head 7)
(Reserve)
D8(Head 8)
(Reserve)
D9(Head 9)
(Reserve)
Bit position
Description
bit0
10 second cycle flicker signal
bit1 to 15
(Reserve)
bit15
bit14
..................
bit2
bit1
bit0
Station
No. 15
Station
No. 14
..................
Station
No. 2
Station
No. 1
Station
No. 0
OFF
ON
5sec
5sec
Device
value
Action
0
The master station accesses all the slave stations
(station 0 to 15). When the multi-drop system
information is not used, the operation is the same.
Other
than 0
Turning on the bit corresponding to a station No.
disconnects the specified slave station from the
master station.
1...Connected
0...Unconnected
bit15
bit14
..........
bit2
bit1
bit0
Station
No. 15
Station
No. 14
..........
Station
No. 2
Station
No. 1
Station
No. 0
Summary of Contents for GT15
Page 2: ......
Page 34: ...A 32 ...
Page 92: ......
Page 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Page 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Page 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Page 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Page 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Page 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Page 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Page 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Page 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Page 510: ......
Page 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Page 668: ......
Page 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Page 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Page 714: ......
Page 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Page 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Page 762: ......
Page 860: ...REVISIONS 4 ...
Page 863: ......