8 - 34
8. ETHERNET CONNECTION
8.4 PLC Side Setting
(2) Open settings
The setting is required for all the connected GOTs.
[Controller Setting] and [Ethernet] of GT
Designer3
POINT
POINT
POINT
(3) [Controller Setting] and [Ethernet] of GT
Designer3
For [Controller Setting] and [Ethernet] of GT
Designer3, refer to the following.
8.3.1 Setting communication interface
(Communication settings)
(4) Ethernet setting
When connecting Built-in Ethernet port CPU to a
GOT, the settings items for the network No. and
station No. do not exist at the PLC side. However,
these virtual values must be set on the GOT side.
Therefore, set the network No. and station No.
Set the network No. that is not existed on the
network system and any station No..
(1) Controller setting
(2) Ethernet setting
*1
Set the same value as that of GOT N/W No.
*2
Set a value different from that of the GOT PLC No. and the
PLC No. of other PLCs on the same network.
Item
Set value
Protocol
UDP (fixed)
Open system
MELSOFT connection (fixed)
Host station port No.
(Use default value)
Item
Set value (Use default value)
GOT NET No.
1
GOT PLC No.
1
GOT IP Address
192.168.0.18
GOT Port No. (Communication)
5001
GOT Port No.
(Ethernet Download)
5014
Default Gateway
0.0.0.0
Subnet Mask
255.255.255.0
Retry
3times
Startup Time
3sec
Timeout Time
3sec
Delay Time
0ms
Item
Set value
Ethernet setting
No.1
Host
*
-
N/W No.
1
*1
1
*1
PLC No.
2
*2
3
*2
Type
QnUDE(H),
LCPU
QnUDE(H),
LCPU
IP address
192.168.0.1
192.168.0.2
Port No.
5006 (fixed)
5006 (fixed)
Communication
UDP (fixed)
UDP (fixed)
Summary of Contents for GT15
Page 2: ......
Page 34: ...A 32 ...
Page 92: ......
Page 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Page 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Page 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Page 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Page 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Page 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Page 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Page 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Page 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Page 510: ......
Page 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Page 668: ......
Page 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Page 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Page 714: ......
Page 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Page 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Page 762: ......
Page 860: ...REVISIONS 4 ...
Page 863: ......