GUID-540639DC-734D-45B7-ACAC-9B00C7A1A9D5 V1 EN
Figure 468:
IEC 61850 Configuration Editor Reporting Status Dataset Dialog Screen
Reporting Trigger Options – (for both Unbuffered and Buffered report
control blocks)
Schema 1.4 does not support General Interrogation. Schema 3.0 does
support General Interrogation.
GUID-4D93A983-857E-4D9C-99AA-FA0DBB94B2BF V1 EN
Figure 469:
Report Trigger Options Dialog Screen
•
Data Change/Data Update – For measurements, if the value of the data attribute
exceeds (either lower or higher) the deadband value the report is generated. For
status, if the value of the data attributes changes, the report is generated.
•
Data Update – is treated the same as Data Change.
•
Quality Change – For any measurement or status, the source is a PROCESS. The
settings are SUBSTITUTED values.
If system error or checksum error is detected, the validity are questionable and inaccurate.
If self test fails, then validity is Invalid. Good means there is no abnormal condition of the
1VAC388793-MB A
Section 13
Appendix D IEC 61850 Configuration Editor
TCC300
683
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......