Drive regulators, this setting should be disabled. When disabled, this applies a 3 second
seal-in output.
Neutral Switch Counter
The Neutral Switch Counter is updated each time the neutral input is detected. Neutral
Switch Counter can also preset to any value. The Neutral Switch Counter is a software
counter that is stored in non-volatile memory and has a maximum value of 999,999.
6.2.3.2
Setting the Operation Counter Configuration from the HMI
This feature is not functional unless Input Selection 1 is set to "Switch
Status".
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the "Tap
Settings" menu.
4.
Press the Down arrow pushbutton, as necessary, until the "Operation Counter
Configuration" screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Op Counter Config
1 X C
6.
Utilizing the Up/Down arrow pushbuttons, select the desired counter configuration
for the application (1 X, 2 X, COUNT WINDOW or CAM FOLLOWER), then press
the ENT pushbutton. The following will be displayed reflecting the counter
configuration that was entered.
7.
Press the Down arrow pushbutton, as necessary, until the "Cooper Quick Drive"
screen is displayed.
8.
Press the ENT pushbutton. The following will be displayed.
Cooper Quick Drive
disable C
9.
Utilizing the Up/Down arrow pushbuttons, select ENABLE for a Cooper Quick
Drive regulator. For a Cooper Spring Drive or Direct Drive regulator, leave this
selection "disable".
10. Press the Down arrow pushbutton, as necessary, until the "Cam Follower" screen is
displayed.
11. Press the ENT pushbutton. The following will be displayed.
Cam Follower
1VAC388793-MB A
Section 6
Configuration
TCC300
337
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......