3.16.2
Clearing tap statistics from the HMI
1.
Navigate to the Clear Tap Statistics screen in the Monitor/Tap Information menu.
2.
Press the ENT pushbutton. The control will display the following.
Press ENT to confirm Clearing Tap Stats
3.
Press the ENT pushbutton. The control will briefly display the "Tap Statistics have
been cleared" confirmation and then return to the previous display.
4.
Press the Exit pushbutton to exit Tap Statistics.
3.16.3
Viewing tap statistics from TCC600
1.
Start TCC600, then establish communications with the target control.
2.
Select Monitor/Tap Statistics from the TCC600 toolbar. TCC600 will display a "Tap
Statistics" screen.
GUID-29DEE835-D924-4505-BC5A-219A1A325DDA V1 EN
Figure 48:
Tap Statistics Screen
By pointing the mouse to any bar, the corresponding tap statistic will
be highlighted as well as displayed in a tool tip.
The "Tap Statistics" screen includes the capability to Refresh the screen display,
Reset All displayed values, and save the data to a ".csv" file which can be read by a
spreadsheet program.
Selecting "Reset All" will clear the Individual Tap Wear Alarm in the Metering &
Status screen.
Section 3
1VAC388793-MB A
Operation
94
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......