Figure 364:
Contact KeepTrack 1N Neutral Tap Configuration Dialog Screen
This feature will allow the physical neutral input to automatically calibrate the tap position
to whatever the Neutral Tap Position setting is set to. The recalibrating "neutral" input can
be set for any tap position not just neutral. Also, the Abnormal Tap Position Alarm will
function based on this setting instead of 0. For example, if the Neutral Tap position setting
is 9R, then an Abnormal Tap Position alarm will occur if the physical neutral input is
received with tap position not indicating 8R, 9R, or 10R.
The Neutral Tap Configuration window allows the user to program the following settings:
1. The full tap range of the tapchanger from highest tap to lowest tap (–33...+33)
2. Assign the neutral tap position based on the tapchanger mechanism
3. Assign the number of neutrals based on the tapchanger mechanism
4. Assign a resting tap to communicate tapchanger position when stopped on neutral
5. Assign which neutral taps have an associated closed neutral contact
6. Select Cam Follower as the Operation Counter configuration if desired
Section 6
1VAC388793-MB A
Configuration
462
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......