Frequency
The control provides for real-time metering of the line frequency. If the control is a 60 Hz
model, the operating frequency is 55 to 65 Hz; if the control is a 50 Hz model, the operating
frequency is 45 to 55 Hz.
V
S
S
L
SL
Regulator
Bypass
Arrestor
I
PRI
Source
Voltage
I
L
0.2 A
Nominal
Load Current
Main CT
Primary
Current
V
PRI
Primary
Voltage
120 V
Nominal
VT
V
LOC
Compensated
Voltage
V
COMP
Theoretical
Load Center
Transmission/
Distribution Line
NOTE
: The VT and CT are usually integral to the regulator.
Indicates calculated quantities
GUID-A89B422C-1E9B-4D1B-88FD-E533FF66A54F V1 EN
Figure 35:
Secondary Quantity Metering and Primary Quantity Calculations for
Regulator Applications
Section 3
1VAC388793-MB A
Operation
58
TCC300
User Manual