Figure 353:
Configuration Dialog Screen
4.
From the Paralleling Options section of the Configuration dialog screen, enter the
following settings consistent with the control's position in the Control Network
Map:
•
Number of Devices – Total number of controls in the Delta VAr Peer to Peer
Paralleling scheme determined in Step 1, (2 to 16).
•
Sensitivity (-4.0 to +4.0)
•
Reactive Circulating Current Limit
Range and units are dependent on the Aux Current Transformer units display setting
in TCC300.
Table 61:
Reactive Circulating Current Limit values
CT Display
Range
Units
200 mA
5...200
mA
1 A
1)
0.02...1.00
A
5 A
1)
0.1...5.0
A
1) These are calculated from the actual 200 mA connected current.
•
Paralleling Address (Control Network Map position, 1 to X)
•
Peer to Peer Update Speed (1000 to 10000 ms)
•
MVA Rating (1.0 to 1000.0)
•
Peer to Peer Current Multiplier Correction (20 to 500 %)
Section 6
1VAC388793-MB A
Configuration
442
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......