GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 264:
Setpoints Successfully Written To The Control Dialog Screen
6.2.3.6
Resetting the Resettable Operation Counter from the HMI
The resettable operation counter operates with the method selected by X1, X2, Count
Window or Cam Follower. This counter can be reset to zero.
1.
Press the Left Arrow (MNTR Hot Button) pushbutton to wake the unit. The menu
will advance to "MONITOR".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Metering
3.
Press the Right or Left arrow pushbutton, as necessary to advance to the "Tap
Information" screen.
4.
Press the Down arrow pushbutton, as necessary, to navigate to the "Resettable
Counter" menu.
5.
Press ENT, a flashing "R" will be displayed. Press ENT again to reset the Operations
Counter.
6.2.3.7
Resetting the Resettable Operation Counter from TCC600
1.
Select
Setup/Tap Settings
from the TCC600 toolbar. TCC600 will display the Tap
Settings dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
341
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......