The user should always verify proper connections by consulting the nameplate on the
regulator tank. The user is cautioned that the nameplate on the control cabinet could
possibly be incorrect if the control has ever been replaced. If the serial number on the
control cabinet matches the serial number on the regulator tank or nameplate, the control
cabinet nameplate may be consulted for proper jumper configuration.
6.2.15.1
Setting Regulator Type from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the
"Nameplate" menu.
4.
Press the Down arrow pushbutton, as necessary, until the "Regulator Type" screen
is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Regulator Type
TYPE A C
6.
Utilizing the Up/Down arrow pushbuttons, select the desired Regulator Type (Type
A or Type B), then press the ENT pushbutton.
6.2.15.2
Setting Regulator Type from TCC600
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
387
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......